EX9060AB-MTCP - 5-channel Digital Input and 3 RELAY output Module
DI*5(Dry/Wet Contact; Isolation) & 3 Relay(0.6A@125VAC; 2A@30VDC)Output(Form A(RL1); Form C(RL2&RL3))& DIO Sync (Mirror Local DI to DO) & Auto-Off Time of DO
Descripción
EX-9060A-MTCP provides 5 isolated digital input channels and 3 relay output channels. All input channels are single ended with common source/ground and support input latch function for important signal handling. Mean while, these DI channels allow to be used as 500Hz counter. All relay output channels are differential with individually common . Opposite to the intelligent DI functions, the EX-9060A-MTCP Digital Output channels also support Auto-Off Time of digital output and DIO Synchronization function.
- Digital input : Isolated single ended with common source/ground.
- Channel : 5 channels (DI0~DI4).
- Input Level : Logic level status can be inversed via ASCII/Modbus command.
- Dry Contact : Single ended with common ground.
- Logic level 1(active), Close to DI.GND
- Logic level 0 (inactive), Open
- Wet Contact : To use Wet Contact , the DI.GND pin must be opened.
- Logic level 1 (active), +4V to +30VDC max.
- Logic level 0 (inactive), +2VDC max.
- Input Impedance : 3K ohm(Wet Contact)
- Counter mode : Supports up to 500Hz counter(by software,32-bit + 1-bit overflow)
- Optical Isolation Voltage: 3750Vrms
- Relay Output : RL1, RL2, RL3
- Output channels : 3 relay output channels (RL1: Form A, RL2, RL3 Form C).
- Surge strength : 500V
- Relay contact rating : 0.6A/125Vac, 2A/30Vdc
- Operate Time : 3mS max.
- Release Time : 2mS max.
- Min Life : 5*105 ops
- Pulse Output : Each channel supports 500Hz pulse output
- Display : 5 digital input & 3 Relay output status LED
- Power requirements : Unregulated, +10V ~ +30 VDC
- Power Consumption : 1.8 W (Typical)